The Honeywell FS-TSDO-0824 is a high-integrity digital output module engineered for safety-critical automation systems. Designed for integration within the Honeywell Safety Manager (Fail Safe) architecture, this module provides 8 isolated output channels capable of controlling solenoids, actuators, and relays while maintaining fail-safe operation. It is certified for SIL 2 and ensures that any fault condition forces outputs to a predefined safe state.
High Reliability and Diagnostics
Monitors internal circuits and field wiring for shorts, open circuits, and cross-channel interference
Includes watchdog timers for self-checking critical components
Diagnostic LEDs for Run, Fail, and individual channel status
Output Specifications
8 independent digital output channels
Nominal voltage: 24 VDC (maximum 36 VDC)
Current capacity: up to 2 A per channel (load-dependent)
Galvanic isolation between logic and field circuits for surge protection
Fail-Safe and Redundancy
Executes automatic safe shutdown on communication loss or critical fault
Supports redundant pairing for increased system availability
Hot-swappable in redundant configurations to minimize downtime
Industrial-Grade Design
Operating temperature: -40°C to +75°C
DIN rail (TS32 / TS35 x 7.5) or panel mount
Robust against electromagnetic interference (EMI) and harsh environments
Compact dimensions: 60 × 70 × 58 mm (D × W × H)
| Feature | Specification |
|---|---|
| Module Type | Fail-Safe Digital Output (TSDO) |
| Channels | 8 |
| Nominal Voltage | 24 VDC |
| Max Voltage | 36 VDC |
| Output Current | Up to 2 A per channel |
| Safety Integrity Level | SIL 2 certified |
| Response Time | High-speed switching |
| Diagnostics | Integrated channel and system monitoring |
| Isolation | Galvanic separation between field and logic |
| Mounting | DIN rail TS32/TS35 x 7.5, panel mount |
| Operating Temp | -40°C to +75°C |
| Dimensions | 60 × 70 × 58 mm |
The FS-TSDO-0824 is suitable for critical SIS loops including Emergency Shutdown (ESD), Fire and Gas (F&G), and other high-integrity process control systems. Its fast, reliable outputs and fail-safe design make it ideal for scenarios requiring SIL-certified operation.
Q: Can this module be used in SIL 3 systems?
A: Yes, it can be configured in redundant pairs to meet higher SIL requirements, although individually it is SIL 2 certified.
Q: Is it safe to replace this module while the system is running?
A: Hot-swapping is supported only when configured redundantly to maintain continuous operation.
Q: What loads can each output channel drive?
A: Each channel supports up to 2 A, suitable for solenoids, relays, and small actuators.
Q: How do I monitor the module status?
A: Front-panel LEDs indicate system Run, Fail, and individual channel conditions for rapid diagnostics.